Specifications
Protect 1.M: Modern high-performance UPS system for the IT sector.
Classification VFI SS 111 according to IEC 62040-3
Protect 1.M Protect 1.M
UPS MODULE System cubicleMAX. (6 x 4 kVA)
Type rating 4 kVA 24 kVA
2.8 kW 16.8 kW
n+x technology
UPS Input
Nominal connection voltage (automatic detection) 230 Vac (1/N/PE~) or 400/230 Vac (3/N/PE~)
Voltage range without battery operation 160–300 Vac (1 ph~) or 277–520 Vac (3 ph~)
Frequency 50 Hz/60 Hz
±
4 Hz
Current consumption (max.) 22 A (1 ph~) or/7.3 A (3 ph~) 132 A (1 ph~) or/44 A (3 ph~)
Mains current (system disturbance factor) l 0.98
UPS Output
Rated output voltage 220 Vac/230 Vac/240 Vac
±
2 % (adjustable)
Frequency in battery operation 50 Hz/60 Hz
±
0.2 Hz
Nominal output current 17.4 A 104.4 A
Changeover time in the event of a mains failure 0 ms (without interruption)
Voltage curve sinusoidal THD < 3 %
Overload capacity (online mode) 125 % for 30 s/130 % for 2 s
then switchover to integrated bypass 0 ms (without interruption)
Crest factor 3
BATTERY
Nominal DC voltage (intermediate circuit) 120 Vdc
Charging characteristics (default) CVCC curve (trickle charge voltage 137 Vdc/charging current max. 3.5 Adc/module)
Autonomy time freely selectable and expandable with external battery modules
(standard available modules with 28, 42 or 65 Ah)
Service life: 10–12 years according to EUROBAT
Exhaustive discharge protection/protection against excess load yes
COMMUNICATION
Interfaces (dual-monitoring) RS232/RS485 (with status messages and measured values),
Expansion slot (for potential-free contacts, USB, SNMP)
Shutdown software (on CD) 5 network licences included in delivery, for all major operating systems
(e. g. Windows, Linux, Mac, Unix, FreeBSD, Novell, Sun etc.)
Alarms (acoustic/optical) graphic LCD display with digital indication of the input and
output parameters (voltage, frequency, power, etc.),
Battery parameters including detailed fault diagnosis
via password-protected level, additional LED display for
status messages/central fault indication
GENERAL DATA
Efficiency AC-AC (at full load) > 89 % > 88 %
Inherent noise (1m distance) < 55 dB (A) < 62 dB (A)
Operating temperature range 0°-40°C
EMC Conformity EN 50091-2, EN 61000-3-2, EN 61000-3-3
EMC emitted interference EN 61000-6-3 Class A
Humidity 20 %–90 %
Installation height up to 1500 m at nominal output
Housing colour Blackline
Dimensions of UPS approx. W x H x D (mm) 442 x 965 x 700 (chassis)/module each: 405 x 87 x 530
Dimensions of battery cubicle approx. W x H x D (mm) 442 x 965 x 700
Weight of UPS 75 kg (chassis) + 15 kg per module
Weight of battery cubicle approx. MBP 28: 160 kg, MBP 42: 200 kg, MBP 56: 255 kg, MBP 65: 270 kg,
MBP 84: 335 kg
Scope of delivery Parallel operation cable, communication cable,
management software "CompuWatch" (CD), operating instructions
Conformity CE
Page view 16
1 2 ... 12 13 14 15 16 17 18 19 20 21 22 23 24