Technical data
Type voltage ...H1
230V -57%* +10% > 99V
400V -57%* +10% > 172V
500V -57%* +10% > 215V
600V -57%* +10% > 258V
Type voltage ...H RL1 and ...H RLP1 without additional 24V electronics supply
230V -15% +10% 230V -57%* +10% > 99V
400V -15% +10% 400V -57%* +10% > 172V
500V -15% +10% 500V -57%* +10% > 215V
600V -15%*+10% 600V -57%* +10% > 258V
*Additional electronics supply
The additional control voltage supply can be AC or DC (6 W per device / 15VA / not grounded).
Normally the supply of the Master modules is sufficient.
24VAC +10% /-20%; 24VDC +18V to +32V
Mains frequency
All types 47 Hz to 63 Hz;
Max. frequency change 5% per half wave
Load type
Ohmic load
Ohmic load with Rwarm/Rcold ratio up to 6, peak current limiting to Î=3xInom (for ...H RLP1 + HRL 1
in VAR operation)
Transformer load
Thyro-A 2A: symmetrical load
Operating modes
TAKT = Full wave switch principle
VAR = Phase angle principle
QTM = Half wave switch principle (Quick Takt Mode) (only for types 1A)
Setpoint inputs
2 setpoint inputs (SELV, PELV), isolated from the system.
- Setpoint 1: analog setpoint input
Signal ranges:
0(4) - 20mA Ri = approx. 250Ω
0(1) - 5V Ri = approx. 44kΩ
0(2) - 10V Ri = approx. 88kΩ
- Setpoint 2: optional bus interface, connection of higher level PC or automation system.
Control characteristic
Each controller (e.g. temperature controller), with an output signal in the range of 0-20mA / 0-5V / 0-10V, can
be adapted to the power controller.