AEG-Refrigeration 292 5209
74
VH34-AUK 06.94
Santo 2941i longfresh E-Nr.: 621 370 121 (R12)
Santo 2902i longfresh E-Nr.: 621 371 022 (R134A)
5.2.2.Refrigeration technology
condenser
refrigeration evaporator
magnetic valve
compressor ` longfresh evaporator
5.2.3.Compressor control
The compressor is activated via the refrigeration fan or via the longfresh cooling fan.
Depending on the air sensor condition, the electronic activates the following functions:
a) Both cooling fans are warmer than the cut-in value:
- compressor ON
- magnetic valve without voltage, i.e. refrigerator and longfresh compartment are
cooling
b) The refrigeration fan is warmer than the cut-in value, the longfresh air sensor is between
ON- and OFF value:
- compressor ON
- magnetic valve without voltage, i.e. refrigerator and longfresh compartment are
cooling
- longfresh fan cycles, i.e. cooling performance in longfresh compartment is
reduced.