Switch Mode Power Supply AC 7000
Page 12 of 24 0208 BAL, en
5.3 Monitoring
5.3.1 Mains Monitoring
The mains monitoring assembly fulfils various functions. It ensures
the intrinsic safety of the unit against overloads and overvoltages with
fixed switching point settings.
The response values (switching points) are given in the technical data
(refer to Chapter 11).
Off
On
Und e rvo lt a g e
Overvoltage
Hysteresis
(Shutdown hysteresis range)
U
mains
[V]
Figure 3:
Phase failure monitoring
- The mains monitoring device detects phase failure and
switches the unit off. When the phase is registered the unit
automatically resumes operation with a "soft start".
Mains undervoltage monitoring
- The unit is switch off if the mains supply drops below the
switching point. When the hysteresis voltage is exceeded the
unit automatically resumes operation with a "soft start".
Mains overvoltage monitoring
- When the maximum permissible mains voltage is exceeded
the SMPS is stopped for the duration of the overvoltage.
When the voltage level drops below the hysteresis voltage the
unit automatically resumes operation with a "soft start".
5.3.2 Output Monitoring
The setting potentiometers and the LED indicators for the following
monitored functions are located on the front plate:
Overtemperature monitoring ϑ
G
with deactivation and latching.
DC-overvoltage indicator U
A
>
with deactivation and latching
(response delay t = 10 ms)
Adjustment with U
A
> potentiometer
DC-undervoltage indicator U
A
<
without delay, without latching
(response delay t = 2,8 s)
Adjustment with U
A
< potentiometer