Device application conditions
Built-in device (VDE0160) EN 50 178
General requirements EN 60146-1-1
Design, vertical installation
Operating conditions EN 60 146-1-1; ch. 2.5
Area of application, industrial CISPR 6
Temperature behaviour EN 60 146-1-1; ch. 2.2
Storage temperature D -25°C - +55°C
Transport temperature E -25°C - +70°C
Operating temperature better B -10°C - +35°C
with forced ventilation (from 280 A)
-10 °C - +45 °C with natural air cooling
-10 °C - +55 °C with reduced type current -2%/°C
Load category 1 EN 60 146-1-1 P.2
Humidity class B EN 50 178 Tab. 7 (EN 60 721)
Overvoltage category III EN 50 178 Tab. 3 (849V)
Degree of contamination 2 EN 50 178 Tab. 2
Air pressure 900 mbar * 1000 m above sea level
Degree of protection IP00 EN 69 529
Protection class I EN 50178 chap. 3
Air and creepage distances housing / mains potential > 5.5 mm
housing / control pot. > 1 mm
mains volt. / control pot. > 10 mm
mains volt. among each other 2.5 mm
Mechanical shocks EN 50 178 chap. 6.2.1
Test voltage EN 50 178 Tab. 18
Tests in acc. with EN 60 146-1-1 4.
EMC emitted interference EN 61000-6-4
Radio interference suppression
Control unit Class A EN 55011; CISPR 11
EMC interference immunity EN 61000-6-2
Compatibility level Class 3 EN 61000-2-4
ESD 8 kV (A) EN 61000-4-2
Electromagnetic fields 10 V/m EN 61000-4-3
Burst mains lines 2kV (A) EN 61000-4-4
control lines 2kV (A)
Surge mains lines 2kV
control lines asym. EN 61000-4-5
1 kV sym. EN 61000-4-5
0.5kV
Conducted EN 61000-4-6
Page view 8