FIG. 11 RELAY K4
9.4 GENERAL (PURPOSE)
Voltage regulation in local networks – also see Chapter 1: General Description
9.5 ON SITE POWER SUPPLY OF THE Thyrobox VR
For the on site power supply of the Thyrobox VR (for activation, measurement, regulation, for
monitoring and internal notifications) the Thyrobox VR takes its auxiliary supply directly from the
local network; 3/PEN, 230 VAC, 10 A.
For service purposes a Euro plug socket (X20) with 10 A fuse is installed in addition which makes
230 VAC available.
9.6 SWITCHING ON AND OFF
Switching the Thyrobox VR on takes place under adherence to and in accordance with the information
in Chapter 11, Commissioning. For switching off the necessary information is contained in Chapter
13, Decommissioning. Switching the Thyrobox VR on and off via remote control is not possible with
the standard set-up.
9.7 TEMPERATURE MONITORING
Cabinet:
Temperature capture system with a sensor PT1000 built into the interior of the cabinet captures the
interior temperature of the Thyrobox VR and activates the front fan via the Thyro-P control device
A11.
Transformer:
To protect the transformers, temperature sensors are built in. There are two activation thresholds:
• at rst threshold (CT1.1, CT2.1, CT3.1) a relay switches the front fan on.
at second threshold (CT1.2, CT2.2, CT3.2) the sensor switches the input of the relevant Thyro-P
control device, which then sets the regulator stop of the phase in question and deactivates the re-
gulation of this phase (current flow is retained in this phase, however, without voltage regulation).
9.8 SAFETY DEVICES
9.8.1 LIGHTNING CURRENT AND SURGE ARRESTER
The integrated lightning current and surge arrester (F2) serves to discharge overvoltages and over-
currents.
9.8.2 TRANSFORMER PROTECTION
Surge and attenuation elements are in place to protect the transformers.
fan test by
manual operation of K4