4.3.6 ADAPTING ANALOG OUTPUT (SCALE)
(ONLY FOR ...H RL1 AND ...H RLP1)
The scale of the analog output is adapted with potentiometer R204
SCALE OUTPUT, if, for example, the scale of the display does not
correspond to the nominal data (see page 42, Analog output).
SETTING 1A (H, HRL1, HRLP1) AT 2A (HRLP1) AT
(DEFAULT = 0-20MA, U-, I-, P DISPLAY - P DISPLAY
CORRESPONDS TO 2A (H, HRL1, HRLP1) AT POTENTIOMETER R204
TYPE VALUE (CURRENT/ U-, I DISPLAY SCALE OUTPUT
VOLTAGE/POWER) POTENTIOMETER R204
SCALE OUTPUT
Potentiometer turns 3.6 turns * (type value power 4.16 turns * (P
type power controller
/
(from left stop) controller/scale end value) scale end value)
Setting aid, analog output 4 mA * (type value power 4.62 mA * (P
type power controller
/
in mA controller/scale end value) scale end value)
(Switch S1.10 = „OFF“)
Setting aid, analog output 2 V * (type value power 2.13 V * (P
type power controller
/
in volts controller/scale end value) scale end value)
(Switch S1.10 = „ON“)
TAB. 6A ANALOG OUTPUT (SCALE) THYRO-A 1A, 2A
SETTING 3A (H, HRL1) AT 3A (HRLP1) AT
(DEFAULT = 0-20MA, U-, I DISPLAY - P DISPLAY *
1
CORRESPONDS TO POTENTIOMETER R204 POTENTIOMETER R204
TYPE VALUE (CURRENT/ SCALE OUTPUT SCALE OUTPUT
VOLTAGE/POWER)
Potentiometer turns 3.6 turns * (type value power 6.24 turns * (P
type power controller
/
(from left stop) controller/scale end value) scale end value)
Setting aid, analog output 4 mA * (type value power 6.93 mA * (P
type power controller
/
in mA controller/scale end value) scale end value)
(Switch S1.10 = „OFF“)
Setting aid, analog output 2 V * (type value power 3.46 V * (P
type power controller
/
in volts controller/scale end value) scale end value)
(Switch S1.10 = „ON“)
TAB. 6B ANALOG OUTPUT (SCALE) THYRO-A 3 A
Analog output: X2.9 (+); X2.5 (ground) *
1
only with ...H RLP1
Example adaptation at the analog output
Thyro-A 3A 400-30 H RLP1 (U
type
= 400 V, I
type
= 30 A, P
type
= 20.7 kW)
Measuring instrument for 4-20 mA with scale 20 kW
SETTING AID
Setting R204: 6.24 * (20.7 kW/20 kW) 6.5 turns
(from left stop)
Setting aid in mA: 6.93 mA * (20.7 kW/20 kW) 7.17 mA
Setting aid in V: 3.46 V * (20.7 kW/20 kW) 3.58 V
4.3.7 SETTING LOAD MONITORING
(UNDERCURRENT MONITORING)
(only for ...H RL1 and ...H RLP1)
This function enables a freely selectable absolute current limit to be
monitored. The value can be set using the R205 potentiometer or the
Thyro-Tool Family. During the configuration process via potentiometer
the monitoring value will be indicated at the analog output. This moni-
toring of absolute values is suitable for one or several load resistors set
up in parallel. Basically the effective value of the current measured is
continually compared with a configurable absolute current limit for
undercurrent.
If it drops below this limit message is sent. In the case of resistors
set up in parallel, by setting the respective undercurrent limit can be
selected a partial load break.
Set load monitoring on the potentiometer R205 LOAD FAULT. The
default setting of this monitoring is OFF (=left stop of the potentio-
meter R205).
A measuring instrument connected to the analog output can be used
as setting aid (see page 43, Potentiometer). If the actual value is fallen
below the set value, a message is sent (LED, by bus and fault signalling
relay K1).
NOTE
Remarks on settings / tables
- Settings over 90% and fewer than 10% not make sense. If the load
currents are considerably less than the nominal currents of the power
controller, consider using a smaller power controller.
- In operating mode VAR, monitoring is blocked for large control angles
(for load with neutral conductor a>140°el., for load without neutral