Thyro 3A
Load with common star point with neutral conductor (1)
Load with separate star point without neutral conductor (2)
Load in open delta connection (3)
DANGER
Dangers during Installation
Risk of injury / Risk of damage to the device or plant
> Observe all safety regulations in the safety chapter
DANGER
Unsafe system due to incorrect installation
The plant cannot be operated safely and poses a threat
to persons.
> Only install the device in an upright position.
> Ensure sufficient ventilation of the cabinet if mounted in a cabinet.
> Observe minimum spacing (Clearance: 150 mm above, 100 mm
below). The devices can be installed next to each other without
spacing between.
> Ensure that the device cannot be heated up by heat sources below
it. (The power loss is given in the type overview table, see page 83,
Technical data)
> Ground the device in accordance with local regulations. (grounding
screw / nut for protective conductor connection to fixing adapter).
Grounding also serves for EMC means (Y capacitor 4.7 nF).
CAUTION
Use of incorrect connection cables
Incorrect connection cables can lead to malfunctions. Use shielded
control conductors to connect the control signals.
For use in UL conditions: Only use 60 °C or 75 °C copper conductors
for power connections (as indicated in Technical Data).
5. INSTALLATION
NO. OF
PARALLEL
LOAD
RESISTORS
I
LOAD NOM
/
I
TYPE CONTROLLER
CURRENT
IN CASE
OF FAULT
RECOMMEN-
DED SETTING
FOR
POTI R205
SETTING AID
AT ACTUAL
VALUE OUTPUT
X2.9 [0-10 V]
SETTING AID
AT ACTUAL
VALUE OUTPUT
X2.9 [0-20 mA]
NO. OF POTEN
-
TIOMETER TURN
FROM LEFT STOP
1 100% 0% 50.0% 2.50 V 5.00 mA 7.8
80% 40.0% 2.00 V 4.00 mA 6.7
60% 30.0% 1.50 V 3.00 mA 5.4
40% 20.0% 1.00 V 2.00 mA 4.2
20% 10.0% 0.50 V 1.00 mA 3.0
2 100% 50% 75.0% 3.75 V 7.50 mA 10.9
80% 60.0% 3.00 V 6.00 mA 9.0
60% 45.0% 2.25 V 4.50 mA 7.2
40% 30.0% 1.50 V 3.00 mA 5.4
20% 15.0% 0.75 V 1.50 mA 3.6
3 100% 66% 83.0% 4.15 V 8.30 mA 11.8
80% 66.4% 3.32 V 6.64 mA 9.8
60% 49.8% 2.49 V 4.98 mA 7.8
40% 33.2% 1.66 V 3.32 mA 5.9
20% 16.6% 0.83 V 1.66 mA 3.8
4 100% 75% 87.5% 4.375 V 8.75 mA 12.3
80% 70.0% 3.50 V 7.00 mA 10.3
60% 52.5% 2.625 V 5.25 mA 8.1
40% 35.0% 1.75 V 3.50 mA 6.0
20% 17.5% 0.875 V 1.75 mA 3.9
5 100% 80% 90.0% 4.50 V 9.00 mA 12.7
TAB. 10 OTHER POSSIBILITIES OF LOAD MONITORING