AEG Electrolux THYRO-A Operations Instructions Page 43

  • Download
  • Add to my manuals
  • Print
  • Page
    / 59
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 42
82 83
• Check load of the output:
Check the load at the 5 V DC output. Minimum resistance:
R
min
= 5 k.
• Check all parallel load resistors for current flow.
Error: Load current flows without triggering
• Check „Live Zero“:
Check the alignment of the control characteristics (U, I, live Zero).
If the input is set to 0-20 mA, but the setpoint value however is
4-20 mA, then the controller will always adjust.
• Check thyristor for short circuit:
Check if a pulsed amount of DC is outputted. Test device with a test
load: e.g. 100W light bulbs single phase / in star connection.
Additional electronics supply
The additional control voltage supply can be AC or DC (2 W per
device / 5 VA / not grounded).
Normally the supply of the Master modules is sufficient.
24 V AC +10% /-20%
24 V DC +18 V to +32 V
9. TECHNICAL DATA
TYPE
VOLTAGE
RANGE* EXTENDED RANGE OF MAINS
VOLTAGE**
230 V -15% + 10% -57% + 10% 99 V < U mains 253 V
400 V -15% + 10% -57% + 10% 172 V < U mains 440 V
500 V -15% + 10% -57% + 10% 215 V < U mains 550 V
600 V -15% + 10% -57% + 10% 258 V < U mains 660 V
* with 5 V on X2.8, ** without 5 V on X2.8
TYPE
VOLTAGE
RANGE RANGE OF MAINS VOLTAGE WITHOUT
24 V ELECTRONIC POWER SUPPLY
230 V -15% + 10% 196 V < U mains 253 V
400 V -15% + 10% 340 V < U mains 440 V
500 V -15% + 10% 425 V < U mains 550 V
600 V -15% + 10% 510 V < U mains 660 V
TYPE
VOLTAGE
RANGE*
EXTENDED RANGE OF MAINS VOLTAGE
WITH 24 V ELECTRONIC POWER SUPPLY
230 V -15% + 10% -57% + 10% 99 V < U mains 253 V
400 V -15% + 10% -57% + 10% 172 V < U mains 440 V
500 V -15% + 10% -57% + 10% 215 V < U mains 550 V
600 V -15% + 10% -57% + 10% 258 V < U mains 660 V
Thyro-A…H1
Thyro-A…H RL1, H RLP1
Thyro-A…H RL1, H RLP1
Page view 42