UPS OPERATING INSTRUCTIONSPROTECTA.500PROTECT A. 700PROTECTA.
103 Safety3.1 General Safety InstructionsRead these operating instructions carefully prior to commissioning of the PROTECT A. UPS and obse
11The output may be live, even if the UPS is not connected to the mains supply, as the UPS has its own internal power supply (battery)!For he
12♦ Condensation may occur if the UPS is brought from a cold environment into the room where it is to be installed. The UPS must be absolutely dry pri
13When replacing the battery, the following must be observed:Only ever use an identical, maintenance-free sealed lead battery with the same dat
143.3 CE Certificate
153.4 Technical DataType ratingPROTECT A.500 500 VA / 300 WPROTECT A.700 700 VA / 420 WUPS inputNominal connection voltage 220 / 230 / 240 VacVoltage
16Charging time (to 90 % of rated capacity) 8 hType Sealed, maintenance-freePROTECT A.500 Block battery 12 V / 7 Ahe.g. CSB, type GP1272F2 3-5 years a
17DirectivesThe PROTECT A. meets the product standard EN 50091.The CE mark on the unit confirms compliance with the EC outline directives for 73/23 EE
18Check the content is complete:♦ PROTECT A. with 500 or 700 VA♦ Mains connection cable with shockproof plug acc. to CEE 7/7Second mains connection ca
194.3 Connections, Operating and Display ElementsFrontRear1 Main switch of the UPS(mains switch)2 LED displays:Green LED: Mains/normal operationYellow
2
205 Installation and Operation5.1 CheckRemove the UPS from its transport packaging and check that it has not been damaged in transit. If you find any
215.3 ChargingThe PROTECT A. is supplied with its battery fully charged. Nevertheless, energy may have been lost during transport, so the batt
22iNote that the additional output socket identified in white has a special property (chapter 4.3 / no. 6 / pg.19).This is always live irres
23iThe interfaces are mutually exclusive. There is no provision for simultaneous operation of RS232 and USB.5.7 OperationOnce you have connect
24The connected loads are powered using the monitored and filtered mains voltage, which is additionally stabilised by the integrated A.V.R
25signal. This might occur because the battery undervoltage limit has been reached, if the temperature has risen too high, or it might indicate
266 Displays and Troubleshooting6.1 Warning SoundsWarning soundMeaningSounds every 10 secondsUPS is operating in battery mode.Sounds every secondUPS i
27UPS overload Remove loads that are less importantBattery voltage is too low Charge the battery for at least 8 hoursData backup time is only very sho
287 MaintenanceThe PROTECT A. consists of state-of-the-art, non-wearing components. We do, however, recommend regular visual checks of th
297.1 Battery ReplacementATTENTION: A battery can cause an electric shock, and represents a considerable hazard if handled incorrectly. The following
3Thank you for deciding to purchase the PROTECT A. UPS from AEG Power Solutions.The following safety instructions are an important part of the operat
308 Storage and DisposalStorageLong storage times without charging or discharging the battery at regular intervals may lead to permanent damage o
319 List of Terms 9.1 Technical TerminologyAVR Automatic Voltage RegulationAutomatic voltage regulation against mainsvoltage deviationsDC/DC booster C
32Guarantee CertificateType: …….……………….…...Unit number:…….……………….…...
41 Notes on these Operating InstructionsDuty to provide informationThese operating instructions will help you to install and operate the Uni
5obligations such as warranty agreements, service contracts, etc. entered into by AEG or its representatives without prior notice in the e
6Table of Contents1 Notes on these Operating Instructions ...42 System Overview ...
72 System OverviewiPROTECT A. is an uninterruptible power supply(UPS) for essential loads such as PCs, work-stations, relatively small-sca
8InverterBatteryRectifierLoadMainsLinefilterA. V. R.~~♦ Overvoltage protection (RJ11)for fax, modem and phone♦ CompuWatch software for shutdown, statu
9The static bypass switch is activated in the event of a mains failure. The inverter then takes over the voltage supply of the connected loads, in or