16. TECHNICAL DATA
WEIGHT
Thyrobox VR, circa
Concrete pedestal, circa
Total weight
385 kg
260 kg
645 kg
TYPE Thyrobox VR 125 kVA Thyrobox VR 250 kVA
Thyrobox VR In the case of load flow from
the PV side to the utility (EVU)
side it regulates continuously to
230 V (can be parameterized,
conductor against N); regula-
tion becomes active from 10%
(can be parameterized) of the
nominal current.
In the case of load flow from
the PV side to the utility (EVU)
side it regulates continuously to
230 V (can be parameterized,
conductor against N); regula-
tion becomes active from 10%
(can be parameterized) of the
nominal current.
Set-up location of Thyrobox VR
Suitable for open air installa-
tion
Suitable for open air installa-
tion
Voltage Outer cable voltage 400 V
(3-phase), against PEN 230 V
Outer cable voltage 400 V
(3-phase), against PEN 230 V
Mains frequency 47-63 Hz 47-63 Hz
Throughput power, maximum
125 kVA, 1 cos ϕ 0.8 (in-
ductive) in the case of energy
flow direction from PV to utility
(EVU) (the throughput power
can occur in both load flow
directions).
250 kVA, 1 cos ϕ 0.8 (in-
ductive) in the case of energy
flow direction from PV to utility
(EVU) (the throughput power
can occur in both load flow
directions).
Nominal throughput current
3 x 181 A 3 x 362 A
Control voltage
3 x 230 VAC 3 x 230 VAC
Regulation
Continuous voltage regulation
of the power circuits with VSC
technology
Continuous voltage regulation
of the power circuits with VSC
technology
Accuracy of regulation
1,0% 1,0%
Adjusting range of voltage
0 to -8% 0 to -8%
Efficiency at nominal power
99,6% 99,8%
THD
U
< 1,5% < 1,5%
Setpoint setting
(if required)
locally via Thyro-Tool Family locally via Thyro-Tool Family
Messages
LED notifications on the con-
trol devices Thyro-P
LED notifications on the con-
trol devices Thyro-P
Potential equalization
Grounding via power cable in
the cable distribution
cabinet (PEN bus bar)
Grounding via power cable in
the cable distribution
cabinet (PEN bus bar)
Cooling
Air cooling, with fan Air cooling, with fan
Temperature monitoring
Transformers with 2 sensors
each, interior temperature
measurement of the Thyrobox
VR with sensor PT1000
Transformers with 2 sensors
each, interior temperature
measurement of the Thyrobox
VR with sensor PT1000