The following tables show the various messages and classification of
default settings (X).
Overview Thyro-A …H RL1 und Thyro-A …H RLP1
ERROR MESSAGES PULSE
INHIBITION
FAULT SIGNALLING
RELAY K1
Frequency error X* X*
SYNC error X* X
Device excess temperature X X
Undercurrents in load circuits X
Flash values invalid X* X
Master / slave error X* X
Failure in rotating field / phase X* X
STATUS MESSAGES PULSE
INHIBITION
FAULT SIGNALLING
RELAY K1
Undervoltage in mains X X
Overvoltage in mains
Pulse inhibition -
Voltage limit minimum *
Voltage limit maximum *
Current limit minimum *
Current limit maximum *
U limit *
I limit *
P limit *
* can not be configured
Default settings fault signalling relay K1: Closed circuit principle
Fault signalling relay K1
NO MESSAGES MESSAGES
Closed circuit principle closed open
Open circuit principle open closed
Please refer also to chapter LED messages and chapter Fault signalling
relay K1.