5.8 USING THE ANALOG OUTPUT
(only for ...H RL1 and ...H RLP1)
Switch off mains supply and secure against accidentally being
switched back on.
Connect terminals X2.9 (+) and X2.5 (ground) to a display device.
Ensure the correct polarity!
• Configure the signal level (see page 42, Analog output).
Adapt the signal level to the scale (page 42, Analog output
(Adapting scale)).
5.9 USING THE THYRO-TOOL FAMILY
Switch off mains supply and secure against accidentally being
switched back on.
• Remove connector (connection to slave) of terminal X22.
• Plug PC interface RS232 with the „Thyro-A“ side into terminal X22.
• Plug in connector (connection to slave) at PC interface RS232.
Connect serial interface (COM) to PC using RS232 data cable (Order
no.: 0048764; not crossed; connections 2,3,5,4 and 7 used).
> The device can be operated with the Thyro-Tool Family.
Measured values and parameters are displayed in the software.
Extended functions can be set (see page 33, Extended functions).
> Only for operation of the device in Thyro-Tool mode (S1.3 to S1.5 to
ON): All parameters can be set with the Thyro-Tool Family.
NOTE
Switching over defined setpoint on the PC interface
A switch can be connected to terminals X1.2 and X1.3 of the PC inter-
face RS232 to switch over the defined setpoint.
- For contact X1.2 with X1.3: Digital defining of setpoint with Thyro-
Tool Family and temporary Thyro-Tool mode.
- For no contact X1.2 with X1.3: Analog defining of setpoint with terminal
X2.4 (see page 19, Setpoint processing)
15 Terminal X22
17 Serial interface (COM) RS232
18 PC-Interface RS232
19 Connector (Connection to Slave only necessary for Thyro-2A and
Thyro-3A)