DEFAULT SETTINGS OF DIP SWITCH S1
For device configuration, there is a 10-pin DIP switch behind the cover
of the master power unit. The DIP switch is only read in once by the
control device at switch-on or when the mains returns. Before commis-
sioning, the DIP switch must be set to suit the application.
Switch off mains supply and secure against accidentally being
switched back on.
• Remove the cover of the master power unit.
• Set configuration on the DIP switch.
The settings that can be made with the individual switches are described
in the following chapters.
S1. 1 2 3 4 5 6 7
8 9 10
FUNCTION
1A…H1/HRL1 and
2A…H1/HRL1
1 0 Operating mode with TAKT
0 0 0 Control mode with UxU
0 Live Zero setpoint with 0 mA
1 1 Setpoint input with 0-20 mA
0 Live Zero analog output only for HRL1
1 Analog output 10 V with 0-10 V/
20 mA only for HRL1
1A…HRLP1 and
2A…HRLP1
1 0 Operating mode with TAKT
1 0 1 Control mode with P
0 Live Zero setpoint with 0 mA
1 1 Setpoint input with 0-20 mA
0 Live Zero analog output
1 Analog output 10 V with 0-10 V/20 mA
3A…H1/HRL1 0 1 Operating mode with VAR
0 0 0 Control mode with UxU
0 Live Zero setpoint with 0 mA
1 1 Setpoint input with 0-20 mA
0 Live Zero analog output only for HRL1
1 Analog output 10 V with 0-10 V/
20 mA only for HRL1
3A…HRLP1 0 1 Operating mode with VAR
0 0 0 Control mode with UxU
0 Live Zero setpoint with 0 mA
1 1 Setpoint input with 0-20 mA
0 Live Zero analog output
1 Analog output 10 V with 0-10 V/20 mA
4.2.1 OPERATING MODE AND LOAD TYPES
S1. 1 2 3 4 5 6 7
8 9 10
FUNCTION
1A/2A 1 0 0 0 0 0 1 1 0 1 TAKT, UxU, Transformer load, 0-20 mA
set point, 0-10 V analog output
1 0 TAKT
0 1 VAR only for 1A
1 1 QTM only for 1A
3A 0 1 0 0 0 0 1 1 0 1 VAR, UxU, Transformer load, 0-20 mA
set point, 0-10 V analog output
0 1
VAR with open delta or star without neutral conductor
1 1 VAR with star with neutral conductor
0 0 VAR with open delta
1 0
TAKT with open delta or star without neutral conductor
Can be set with Thyro-Tool Family
TAKT with delta or star with neutral conductor
TAKT with open delta
Default settings
4.2.2 CONTROL MODE/ANALOG OUTPUT
The highest value of the load voltage or load current is always used for
control and display. The total power is used for power control. If a bus
module or PC is connected, control mode and analog output can be set
separately, e.g. U control with I display.
S1. 1 2 3 4 5 6 7
8 9
10
FUNCTION
FUNCTION R201
H1 1 0 0 0 0 0 1 1 0
1
UxU
Transformer load (phase
angle 1st half-wave)
1 0 UxU with Umax Uload max
0 1 U
Transformer load (phase
angle 1st half-wave)
1 1 U with Umax Uload max
S1. 1 2 3 4 5 6 7
8 9
10
FUNCTION
FUNCTION R201
HRL1/HRLP1 0 0 0
UxU with analog output Uload
Uload max
1 0 0 U with analog output Uload Uload max
0 1 0 IxI with analog output Iload Uload max
1 1 0 I with analog output Iload Uload max
0 0 1 I with analog output Iload Uload max
1 0 1
UxU with analog output Iload only for HRL1
Uload max
0 1 1
U with analog output Iload only for HRL1
Uload max